How to Soundproof a Drywall Partition Wall
Soundproofing a drywall partition wall against airborne noise (voices, television, music) requires applying the “Mass–Spring–Mass” acoustic principle to block the transmission of sound waves between rooms:
- Increasing mass and damping: High-density drywall panels, combined with heavy, elastic soundproofing membranes, significantly improve the acoustic attenuation index.
- Damping structural vibrations: Using acoustic sealing strips beneath metal profiles (UW/CW) and employing anti-vibration brackets prevents flanking noise transmission.
- Internal absorption: Completely filling the cavity between the profiles with acoustic mineral wool eliminates the “resonance box” effect.
What is airborne noise, and how does it affect lightweight walls?
Unlike impact noise (footsteps, mechanical vibrations transmitted through the structure), airborne noise propagates directly through the air in the form of pressure waves—such as neighbors’ voices, television sounds, or music.
Comparison of Drywall Wall Configurations
When these waves strike a standard, lightweight drywall partition, the structure begins to vibrate and re-emits the sound into the adjacent room, acting much like a loudspeaker diaphragm. To effectively combat this phenomenon, the acoustic system must meet three conditions:
- High mass: Heavy materials resist the passage of sound waves.
- Internal absorption: The wall cavity must be filled with a porous, absorbent material.
- Elastic decoupling: Avoiding rigid contact between the metal profile, the floor, the ceiling, and the masonry.
Acoustic efficiency is measured using the Rw index (expressed in decibels, dB). The higher the Rw value, the better the wall blocks noise:
| Partition wall configuration | Total thickness | Sound reduction index (Rw) | Acoustic comfort level achieved |
|---|---|---|---|
| Single-layer wall (1 plasterboard sheet per side + insulation) | 75 – 100 mm | 38 dB – 42 dB | Low: Conversations at normal volume and television sounds are clearly audible. |
| Double-layer wall (2 plasterboard sheets per side + insulation) | 100 – 125 mm | 48 dB – 52 dB | Medium: Normal conversations are no longer intelligible; only muffled sounds remain. |
| Krongum acoustic system (Double-layer + heavy soundproofing membrane + acoustic insulation) | 110 – 130 mm | 60 dB – 65 dB | Excellent (studio/hotel standard): Substantial blocking of music, television, and loud voices. |
Step-by-step guide for installing a sound-insulated wall
To achieve sound insulation of over 60 dB, follow this technical procedure:
- Decoupling the metal framework: Before securing the perimeter (UW) profiles to the floor, ceiling, and side walls, you must apply a self-adhesive acoustic sealing tape—made of foam or rubber—to the back of the profiles.
- Installing the metal framework and acoustic insulation: Install the vertical (CW) profiles with a center-to-center spacing of 60 cm. Completely fill the cavity between the profiles with basalt or glass mineral wool, specifically designed for acoustic applications.
- Applying the first layer of boards: Attach the first layer of acoustic plasterboard to the metal framework.
- Installing a high-density soundproofing membrane: Adhere a high-density, viscoelastic membrane (such as Krongum Soundblock) onto the surface of the first layer of plasterboard.
This adds mass without taking up space and dampens vibrations in the board.
- Applying the second layer of boards (staggered): Install the second layer of drywall, ensuring that the joints between the boards are staggered relative to the first layer.
- Edge sealing: Fill the perimeter gap between the boards and the existing walls using an elastic acoustic sealant (do not use standard rigid polyurethane foam).
Common mistakes that ruin soundproofing
- Omitting acoustic tape under profiles: Attaching metal directly to concrete creates a rigid sound bridge, allowing vibrations to pass through unimpeded.
- Installing electrical boxes back-to-back: Cutting openings for electrical boxes in the exact same spot on both sides of the wall creates a direct acoustic gap. Boxes should be offset by at least 30–50 cm from one another.
- Failure to seal joints: A small, unsealed opening in the wall can reduce the overall acoustic performance of the system by as much as 10–15 dB.
Frequently Asked Questions
No. Mineral wool acts only as a sound absorber (it stops echoes within the cavity). Without mass (heavy panels) and viscoelastic damping (a soundproofing membrane), low- and medium-frequency airborne noise will easily pass through the wall.
An acoustic partition lining or a thin, independent wall cladding—consisting of a soundproofing membrane and plasterboard—will take up between 5 cm and 8 cm of the room’s depth.